Controlling device Softmaster® ROE 1 for the automated operation of reverse-osmosis systems.
Application
- reverse osmosis plants with 1 conductivity measurement
Measuring range
0,1 – 50.000 μS/cm
0,01 – 5,0 cm-1 cell constant
Technical Data
- Mains connection: 230–240 VAC, 115 VAC, 24 VAC +/-10% all 50–60Hz
- Power consumption: max. 9 VA
- Protection type: I
- Protection class: IP 65
- Dimensions (W x H x D): 270 x 295 x 130 mm / 10.6″ x 11.6″ x 5.1″
- Control panel cut-out: 262 x 146 mm, +1 mm / / 10.3″ x 5.7″
- Installation depth: ca. 90 mm / 3.5″
- Front frame dimensions: 270 x 155 mm / 10.6″ x 6.1″
- Weight: approx. 2.3 kg / 5 lbs
- Potential-free relay outputs for filters, 2 regeneration valves, 2 additional programmes and error messages
- output for metering pulse
- 12 V power supply
- Port for conductivity probe for permeate and temperature sensor
- Five potential-free relay outputs for pump, inlet valve, flushing valve, measuring and error message output
- Five inputs for water deficiency message, overpressure message motor protection, storage tank FULL/EMPTY, system stop
- menu navigation in German, English, French, Italian, Dutch, Polish